Leave a messageThe ZW8-12/C series vacuum Circuit Breaker is an Outdoor High-voltage Switchgear with a rated voltage of 12KV and three-phase AC
50Hz. It is mainly used to open and close the load current, overload current, and sho比-circuit current of rural power grids, urban power
grids, and small power systems. The overall structure of this product is a three-phase common box type, with a three-phase vacuum arc
extinguishing type placed in a metal box. It uses SMC Insulation materials for inter phase insulation and ground insulation, with reliable peformance and high insulation strength.
ZW8-12G is a combination of ZW8-12 circuit breaker and isolation switch, called a combination circuit breaker, which can be used as a
segmented switch.
The operating mechanism of this series of products is the CT23 spring energy storage operating mechanism, which is divided into two types: electric and manual.
1.Main technical parameters
Number | Project | Unit | Parameter | |||||
1 | Rated voltage | KV | 12 | |||||
2 | Rated current | A | 630(1250) | |||||
3 | Rated short-circuit breaking current | KA | 6.3 | 12.5 | 20 | |||
4 | Rated short-circuit making current (peak) | KA | 16 | 31.5 | 50 | |||
5 | Rated peak withstand current | KA | 16 | 31.5 | 50 | |||
6 | Rated short-term withstand current | KA | 6.3 | 12.5 | 20 | |||
7 | Power frequency withstand voltage (dy) | 42 | ||||||
Lightning impulse withstand voltage (peak) | 75 | |||||||
8 | Rated operating sequence | Fen-0.3S-180S-Fen | ||||||
9 | Mechanical lifespan | Once | 10000 | |||||
10 | Rated short-circuit breaking current breaking frequency | Once | 30 | |||||
11 | Rated closing voltage of operating mechanism | V | AC、DC 110,220 | |||||
12 | Rated opening voltage of operating mechanism | V | AC、DC 110,220 | |||||
13 | Contact opening distance | mm | 11±1 | |||||
14 | Ove比ravel (compression length of contact spring) | mm | 3- | +1 -0.3 | ||||
15 | Three phase opening and closing asynchrony | ms | ≤2 | |||||
16 | Contact closing bounce time | ms | ≤2 | |||||
17 | Average opening speed | m/s | 1.2±0.3 | |||||
18 | Average closing speed | m/s | 0.6±0.2 | |||||
19 | Opening time | s | ≤0.06 | |||||
21 | Closing time | s | ≤0.1 | |||||
22 | Resistance of each phase main circuit | μΩ | ≤200 | |||||
23 | Allowable wear accumulation thickness of dynamic and static contacts | mm | 3 |
2.Outline and installation dimension diagram
Series outdoor Vacuum Circuit Breakers
Series Outdoor Vacuum Circuit Breakers
Note: If users have special requirements, they can negotiate with our factory to determine.
Circuit Breaker Installation Tips
Installing a circuit breaker is crucial for safeguarding your electrical system. Proper installation ensures the safety of your home or workplace by preventing electrical hazards. Follow these essential circuit breaker installation tips for a secure and efficient setup.
Before beginning the installation, ensure you choose the correct circuit breaker for your system. Consider the type of electrical system you have (single-phase or three-phase) and the amp rating that matches the wiring size. For instance, a 15-amp breaker should be paired with 14-gauge wire, while a 20-amp breaker needs 12-gauge wire.
Safety is paramount when working with electricity. Always turn off the main power supply before installing a circuit breaker to avoid electrocution or damage to the electrical panel.
Ensure that the electrical panel is in good condition. If it's old or damaged, it might be time for a replacement. The panel should be clean and free of debris to ensure proper breaker installation.
Align the new circuit breaker with the slots in the panel. The breaker should snap into place securely. Make sure the breaker’s metal tab fits correctly into the panel’s bus bar.
Once the breaker is in place, connect the corresponding wires. The black (hot) wire should be attached to the terminal screw on the breaker. The neutral wire (usually white) should be connected to the neutral bus bar, and the ground wire (green or bare) should go to the ground bus bar.
Ensure all wire connections are tight. Loose connections can cause electrical hazards like overheating or fires. Use a screwdriver to tighten each connection securely.
After installation, turn the main power supply back on and test the new circuit breaker. Flip the breaker switch to the "on" position and check if the connected circuit functions correctly. If the breaker trips immediately, recheck the wiring to ensure everything is correctly connected.
Once the circuit breaker is installed and tested, label it clearly. Labeling helps you identify the breaker’s function in Case of future maintenance or troubleshooting.
Periodically check circuit breakers for signs of wear or damage. Over time, breakers may lose their effectiveness. If a breaker trips frequently, it may need to be replaced.
Installing a circuit breaker is essential for a safe and functional electrical system. By following these tips and prioritizing safety, you can ensure proper installation. Always consult a professional electrician if you’re unsure about the process to avoid mistakes and potential hazards.
Tel: +86 13588970775
E-mail: 954518655@qq.com
Fax: +86 0577-62770775
Add: 281 Central Avenue, Yueqing Economic Development Zone,
Yueqing City, Wenzhou City,Zhejiang Province,China
Copyright © 2023 Youkai Electric Co., Ltd All rights reserved
This website uses cookies to ensure you get the best experience on our website.
Comment
(0)