Manager Wang
Leave a messageFLRN36-12D sulfur hexauoride (SF6) high-voltage Load switch is a switchgear with a rated voltage of 12kV, using SF6 gas as the arc extinguishing and Insulation medium. e switch has three internal positions for closing, opening, and grounding, and has the characteristics of small size, easy installation and use, and strong environmental adaptability.
This series of load switches is divided into FLN36-12D (K-type single spring operating mechanism) and FLRN36-1D (A-type double spring operating mechanism)
Seed. The FLRN36-1D model can be combined into a load switch+Fuse combination electrical device and has control and protection functions. It can be used for the protection and control of electrical equipment in power supply and substations, especially suitable for ring main units, cable distribution boxes, and distribution switching stations.
Compliant with standards such as IEC60265, IEC62271, GB3804, GB16926, etc.
1.Main technical parameter
Project | Unit | Parameter | ||||
FLN36-12D | FLRN36-12D | |||||
Rated voltage | kV | 12 | 12 | |||
Rated frequency | Hz | 50 | 50 | |||
Rated current | A | 630 | 125 | |||
Rated short-time withstand current/rated short-circuit duration of load switch | kA/s | 20/3 | - | |||
Rated short-time withstand current/rated short-circuit duration of grounding switch | kA/s | 20/2 | - | |||
Rated peak withstand current and rated short-circuit closing current | kA | 50 | 125(Expect) | |||
Rated breaking current | Active load breaking current | A | 630 | - | ||
Closed loop breaking current | A | 630 | - | |||
5% rated active load breaking current | A | 31.5 | - | |||
Disconnect the cable charging current | A | 10 | - | |||
Disconnect the capacity of the no-load transformer | kV | 1250 | 1250 | |||
Disconnect and transfer current | A | - | 1700 | |||
Expected short-circuit breaking current | kA | - | 50 | |||
Rated insulation level | 1-minute power frequency withstand voltage phase to phase, ground/fracture | kV | 42/48 | 42/48 | ||
Lightning impulse withstand voltage phase to phase, ground /fracture | kV | 75/85 | 75/85 | |||
Mechanical lifespan of main circuit and grounding circuit | 3000/2000 | 2000/2000 | ||||
SF6 rated pressure (gauge pressure at 20 ° C) | MPa | 0.04~0.05 | 0.04~0.05 |
2.Structure and principle
The main circuit and grounding circuit of FLN36-12D load switch are sealed in an insulation shell made of epoxy resin cast with APGI technology, which has the advantages of good insulation peormance and anti pollution environment. e insulation shell is composed of two upper and lower insulation covers, which are lled with SF6 gas with a relative pressure of 0.4 bar inside. e lower insulation cover has explosion-proof measures to ensure that in Case of an accident, the SF6 gas with overpressure is directly sprayed into the channel behind the cabinet, ensuring personal safety.
3. Installation dimensions and external dimensions
Tel: +86 13588970775
E-mail: 954518655@qq.com
Fax: +86 0577-62770775
Add: 281 Central Avenue, Yueqing Economic Development Zone,
Yueqing City, Wenzhou City,Zhejiang Province,China
Copyright © 2023 Youkai Electric Co., Ltd All rights reserved
This website uses cookies to ensure you get the best experience on our website.
Comment
(0)